Calculate cable size, voltage loss and end voltage for LED strip, garden lights and low voltage lighting runs. Results update instantly as you type.

  • Free to use
  • Copper cable, 0.5–6.0mm²
  • Trusted by Australian electricians & DIYers
System voltage The DC output voltage of your LED driver or transformer. Check the label on the power supply — most LED strip is 12V or 24V.
Total wattage connected to this cable run. For LED strip: watts per metre × strip length. e.g. 9.6W/m × 5m = 48W.
W

Total connected wattage on this run.

A

Optional — if entered, this current is used instead of calculating from watts.

The length of the supply cable between the driver and the light — not the LED strip itself. Measure the actual cable path, including any loops or rises.
m
Length measured as Current flows out along one conductor and back along the other. Choose "one-way run" if you measured the distance to the light (we double it for you), or "total loop" if you measured the full out-and-back cable length.

One-way run: the ×2 return path is applied automatically.

Cable size The cross-sectional area of each copper conductor, printed on the cable sheath. Bigger cable = less resistance = less voltage drop.
Copper conductors only. This calculator uses stranded copper resistance values (IEC 60228 at 20°C). Aluminium or copper-clad aluminium (CCA) cable has roughly 60% higher resistance — avoid it for low voltage lighting.
Live result Enter your run
23.69V
Voltage at the end of the cable
2.00 A
Current draw
0.31 V
Voltage drop
1.3%
Drop percentage

Max run on 2.5mm² at ≤3% drop — m

Compare cable sizes for your run

Voltage drop for every common cable size using your inputs above. The smallest cable that passes is highlighted.

Cable size Resistance (Ω/m) Voltage drop Drop % End voltage Result

How the calculation works

No black box — these are the exact formulas behind the numbers above, shown live with your inputs.

The formulas

Current = Watts ÷ Voltage
Voltage drop = 2 × length × current × resistance per metre
Drop % = voltage drop ÷ system voltage × 100

Assumptions

  • Stranded copper conductors, DC resistance per IEC 60228 at 20°C (e.g. 2.5mm² = 0.00741 Ω/m).
  • Two-conductor DC circuit — drop occurs on both the outgoing and return conductor.
  • Pass ≤ 3% drop · Warning 3–5% · Fail > 5%, in line with common low voltage lighting practice.
  • Connector, joint and terminal resistance is not included — keep joins to a minimum on long runs.
  • Resistance rises with temperature (~0.4%/°C) — allow margin for cable in hot roof spaces or conduit in full sun.

Voltage drop, explained simply

What is voltage drop?

Every cable resists the flow of electricity. As current travels along a cable, some voltage is lost overcoming that resistance — so the voltage arriving at your light is always lower than the voltage leaving the driver. That loss is voltage drop. It grows with longer cable, higher current and thinner conductors.

Why it matters for LED strip

LED strip is voltage-sensitive. A 24V strip receiving 22V won't just be slightly dim — brightness falls noticeably, whites drift warmer, and on RGB strip the colour mix shifts. Because the strip itself also has resistance, the LEDs furthest from the feed are hit hardest, producing a visible brightness gradient along the run.

Why 24V beats 12V over distance

Power = volts × amps. Deliver the same wattage at 24V instead of 12V and the current halves. Half the current means half the voltage drop in volts — and because the system voltage doubled too, the drop as a percentage is quartered. The result: a 24V run can go roughly four times further on the same cable. For any run over a few metres, choose 24V.

When to use thicker cable

Step up a cable size whenever the calculator shows more than 3% drop, when a run is long but you're locked into 12V, or when you may add more lights to the circuit later. Doubling the conductor area roughly halves the resistance. Heavier cable costs a little more per metre, but it's far cheaper than re-pulling cable after you notice dim lights.

Split long runs or feed both ends

Past a certain length, thicker cable stops being the smart fix. Splitting one long run into two shorter runs fed from a central driver halves the distance each amp travels. Feeding an LED strip from both ends (or injecting power mid-run) does the same job — voltage drop falls dramatically and brightness evens out across the whole strip.

A worked example

You're feeding 5 metres of 9.6W/m LED strip (48W total) on a 24V system, with the driver 10 metres away on 2.5mm² copper cable:

Current   = 48W ÷ 24V = 2.0A
Drop      = 2 × 10m × 2.0A × 0.00741 Ω/m = 0.30V
Drop %    = 0.30V ÷ 24V × 100 = 1.2%  →  PASS
End volts = 24V − 0.30V = 23.70V

The same load and cable on a 12V system draws 4A and drops 0.59V — a 4.9% loss, right at the edge of failure. Same lights, same cable, four times the percentage drop. That single comparison is why 24V is the default choice for longer LED runs.

Frequently asked questions

What is acceptable voltage drop for LED lighting?
For low voltage LED lighting, aim to keep voltage drop at or below 3% of the system voltage — that's 0.36V on a 12V system or 0.72V on a 24V system. Between 3% and 5%, most LED strip and garden lights will still work, but you may notice slight dimming or colour shift at the far end of the run. Above 5%, brightness loss becomes visible and some fittings may flicker or fail to operate correctly.
Is 24V better than 12V for LED strip?
Yes — for longer runs, 24V is significantly better. At the same wattage, a 24V system draws half the current of a 12V system, and because voltage drop is proportional to current, the drop in volts is halved. The drop as a percentage of system voltage is quartered. In practice, a 24V LED strip can run roughly four times further than a 12V strip on the same cable before hitting the same voltage drop percentage.
How do I calculate voltage drop?
First find the current: divide the load in watts by the system voltage (Current = Watts ÷ Volts). Then multiply: Voltage drop = 2 × cable length (m) × current (A) × cable resistance per metre (Ω/m). The factor of 2 accounts for the current travelling out and back along both conductors. Finally, divide the drop by the system voltage and multiply by 100 for the percentage. For example: 48W at 24V is 2A; over 10m of 2.5mm² copper (0.00741 Ω/m), drop = 2 × 10 × 2 × 0.00741 = 0.30V, or 1.2%.
What cable size should I use for LED strip?
It depends on the load, the system voltage and the cable length. Short feeds under 2–3 metres at low wattage are usually fine on 0.5mm² or 0.75mm². Typical 5–10 metre feeds to a 24V strip suit 1.5mm² to 2.5mm². Long garden runs or high-wattage strips often need 4.0mm² or 6.0mm². Run your exact figures through the calculator above and choose the smallest cable size that keeps voltage drop at or below 3%.
Does cable length affect LED brightness?
Yes. Every metre of cable adds resistance, and resistance causes voltage to drop along the run. LEDs at the end of a long cable receive less voltage than those near the power supply, so they appear dimmer, and on tunable or RGB strips the colour can shift. Doubling the cable length doubles the voltage drop — which is why long runs need thicker cable, a higher system voltage, or power injected at both ends.
Can I power LED strip from both ends?
Yes — feeding power to both ends of an LED strip (or injecting power at the midpoint) is a recommended technique for longer runs. It halves the effective distance current has to travel, which substantially reduces voltage drop and evens out brightness across the strip. Both feeds must come from the same driver, or from supplies with matched output voltage.
This calculator is a guide only. It does not replace AS/NZS wiring rules, manufacturer specifications or professional judgement. In Australia, 240V electrical work must be carried out by a licensed electrician, and some low voltage installations also require one. If in doubt, talk to your sparky.